Products

JCZ5 250A-630A 7.2kV AC Vacuum Contactor

The JCZ5 indoor AC vacuum contactor series covers 7.2 kV and 12 kV, 50 Hz systems with 250 A, 400 A, and 630 A ratings. It is intended for frequent switching of motors, transformers, and capacitive loads; confirm the required voltage, current, and control configuration before ordering.
  • Rated voltage: 7.2 / 12 kV
  • Rated current: 250 A / 400 A / 630 A
  • Rated maximum breaking current: 2,000 A / 3,200 A / 5,040 A (for 250 A / 400 A / 630 A variants)
  • Power-frequency withstand voltage: 42 kV

Description

JCZ5 Series Overview

The JCZ5 indoor AC vacuum contactor is designed for three-phase AC 50 Hz power systems and frequent switching of medium-voltage motors, transformers, and capacitive loads. The published series data covers 7.2 kV and 12 kV variants with rated currents of 250 A, 400 A, or 630 A. Select the voltage, current, and control configuration for the intended circuit rather than treating all listed values as one fixed model.

Operating Conditions

  • Altitude: no more than 1,000 m above sea level
  • Ambient temperature: -5°C to 40°C
  • Maximum 24-hour average temperature: 35°C
  • Relative humidity: no more than 50% at 40°C
  • Pollution degree: Class 3

Electrical Ratings

Parameter Unit 250 A variant 400 A variant 630 A variant
Rated voltage kV 7.2 / 12
Rated current A 250 400 630
Rated closed current (existing specification) A 2,500 4,000 6,300
Rated maximum breaking current A 2,000 3,200 5,040
4 s thermal stability current A 2,500 4,000 6,300
Maximum breaking current (existing specification) A 2,500 4,000 6,300
Power-frequency withstand voltage kV 42
Permitted operating frequency operations/hour 300
Electrical life, AC-3 duty operations 25 × 104
Electrical life, AC-4 duty operations 10 × 104

Control and Operating Data

Parameter Published value
Control-circuit rated voltage AC 110 / 220 V
Closing-coil current ≤ DC 6 / 3 A
Holding-coil current D: DC 0.32 / 0.16 A
Shunt-trip coil current J: DC 2.5 / 1.3 A
Contact distance 1.5 ± 0.5 mm
Average closing speed 0.1–0.25 m/s
Average opening speed 0.3–0.6 m/s
Three-phase opening synchronism ≤ 2 ms
Closing / opening time ≤ 150 / ≤ 50 ms
Resistance at 20°C ≤ 250 μΩ

Application and Selection

The JCZ5 series is intended for repeated circuit making and breaking in motor control, transformer switching, capacitor-bank switching, and related power-distribution duties. The series is available with mechanical latching or electromagnetic holding arrangements.

The page title identifies the 7.2 kV product, while the series specification also lists a 12 kV option. Before ordering, confirm the required system voltage, continuous current, switching duty, control voltage, holding arrangement, and installation conditions. These inputs determine which JCZ5 configuration should be quoted.

Request a Configuration Review

Send the required rated voltage and current, control voltage, load type, expected switching frequency, installation altitude, and ambient-temperature range. Kampa Electric can then check the requested configuration against the published JCZ5 series data.

FAQ

Which voltage and current ratings are listed for the JCZ5 series?

The published series data lists 7.2 kV and 12 kV variants with rated currents of 250 A, 400 A, and 630 A. Confirm the required combination for the intended circuit.

What equipment can the JCZ5 vacuum contactor switch?

The existing product information identifies medium-voltage motors, transformers, and capacitive loads as typical switching duties in 50 Hz power systems.

What operating conditions are specified?

The listed conditions are an altitude up to 1,000 m, ambient temperature from -5°C to 40°C, a 24-hour average no higher than 35°C, relative humidity no higher than 50% at 40°C, and Pollution Degree 3.

What control voltage is listed?

The published control-circuit rated voltage is AC 110 / 220 V. Confirm the required control arrangement and coil configuration before ordering.

What information should I provide for selection?

Provide the rated system voltage and current, control voltage, load type, expected switching frequency, installation altitude, and ambient-temperature range so the requested configuration can be checked against the series data.

Request Quote

Tell us your specifications, quantity, or application scenario and we will reply with a tailored quote.

+86-13362788157 Phone tony@elexpert.cn E-mail Chat on WhatsApp WhatsApp