VZF(R)-12 vacuum load break switch-fuse combination

The VZF(R)-12 vacuum load break switch-fuse combination unit is specially designed for 12kV indoor air-insulated switchgear (AIS). It integrates load switching and fuse protection in a compact, withdrawable handcart, offering reliable short-circuit protection and easy maintenance.

Key Features

Rated voltage: 12kV, rated current: 630A

Breaking capacity: 25kA (short circuit)

Withdrawable handcart design, easy to install and maintain

Vacuum interrupter with triple-sealed insulation

Epoxy “T” pole cast with APG technology

Fuse-blown trip function, ensuring double protection

Full mechanical interlock and visible disconnection

Modular terminal layout for easy wiring replacement

Mechanical Characteristic Parameters

No. Item Unit Parameter
1 Contact gap mm 9±1
2 Contact pressure spring travel mm 4±1
3 Phase center distance mm 210/275
4 Opening/closing time difference ms ≤2
5 Contact closing spring time ms ≤3
6 Average closing speed m/s 0.4~0.8
7 Average opening speed m/s 1.0~1.4
8 Closing time (rated voltage) ms ≤60
9 Opening time (rated voltage) ms ≤30
10 Main circuit resistance ≤250
11 Allowable wear thickness of contacts mm 3

Technical Parameters

No. Name Unit VZF-12/T630-20 Vacuum Load Switch VZFR-12/T125-50 Vacuum Load Switch – Fuse Combination
1 Rated voltage kV 12 12
2 Power frequency withstand voltage (phase/earth) kV 42 42
3 Lightning impulse withstand voltage (phase/earth) kV 75 75
4 Rated current A 630 125 (Fuse)
5 Rated short-circuit breaking current kA 50 (Fuse)
6 Rated short-time withstand current kA 20