Multi-Ratio Current Transformer: Taps, Series Connection and Selection

A multi-ratio current transformer is one core assembly that can be connected to give more than one transformation ratio. The extra ratios arrive by two different routes: reconnecting the primary winding in series or parallel, or bringing out taps partway along the secondary winding. Both routes change the ratio. They do not change it in the same way, and the difference decides whether the unit you ordered still meets its class, its burden and its short-circuit rating at the ratio you actually intend to use.

Most procurement arguments about these units come down to one sentence in an offer: rated 2×600/5 A, 0.2S/5P20, 30/50 VA. That sentence is usually true at one connection and partly untrue at the others. This article sets out the two connection methods, what each does to accuracy, burden and thermal withstand, and the wiring rules that keep a tapped current transformer from becoming a hazard in a panel.

How One Frame Produces Several Ratios

A current transformer is a ratio device held together by ampere-turn balance. Neglecting excitation, the primary ampere-turns equal the secondary ampere-turns:

Ip x Np = Is x Ns, so Is = Ip x Np / Ns and the ratio is Ns / Np.

Two variables sit in that equation, and each one gives a way to offer several ratios from a single unit:

  • Change Np. Split the primary into two identical sections and connect them in series or in parallel. Series doubles the effective primary turns, parallel halves the effective turns per ampere of through current. This gives two ratios in a 2:1 relation, and occasionally three in a 4:2:1 relation.
  • Change Ns. Bring out intermediate terminals from the secondary winding. Using part of the winding reduces the effective secondary turns, and the ratio follows.

The two methods are not interchangeable, because they distribute the same ampere-turns differently. The table below is the short version of everything that follows.

Property at each available ratio Primary series / parallel Secondary taps
Number of ratios 2 (2:1), sometimes 3 (4:2:1) 2 to 5 on one winding, arbitrary steps
Ampere-turns Identical at every ratio Falls with each lower tap
Rated burden, VA Identical at every ratio Falls roughly in proportion to the tap
Accuracy class Identical at every ratio Stated for the full winding only
Accuracy limit factor Identical at every ratio Falls at each lower tap
Short-time thermal current Halved at the lower ratio Unchanged at every ratio
Typical product 2 x 600/5 A, 2 x 1200/5 A utility metering 1200/5 A with X1 to X5 taps

Primary Series and Parallel Connection

The primary is built as two sections of equal turns, brought out to four terminals marked in pairs. Connect the two sections end to end and the through current passes every turn, so the primary ampere-turns double and the ratio divides by two. Connect the two sections side by side and the through current splits between them, so the primary ampere-turns equal those of one section and the ratio doubles.

Because the ampere-turns are the same in both connections, the flux in the core is the same, the excitation current is the same, and the secondary performance is the same. Wound-type units rated 2×600/5 A therefore hold their declared class and burden at both 600/5 A and 1200/5 A. That is the main reason this construction survives in utility metering cabinets, where a load study is often revised after the CT is already installed.

The cost sits in the thermal rating, not in the accuracy. In the series connection each section carries the full through current, so the assembly’s through-current capability is the capability of one section. In the parallel connection each section carries half the through current, so the assembly can pass twice as much before either section reaches its limit. Stated in kiloamperes, the short-time withstand current at the lower ratio is roughly half the figure at the higher ratio.

This matters because the fault level at the installation point does not halve when the site electrician moves the links. A unit sold as 2×600/5 A, 25 kA for 1 s at 1200/5 A is being asked to survive a 25 kA board at 600/5 A, where the same hardware can only claim about 12.5 kA. Ask for the short-time current per connection, not per model, and check it against the board’s prospective fault current and its clearing time.

Diagram comparing primary series and parallel reconnection with secondary taps in a multi-ratio current transformer, showing how each method changes ampere-turns

Secondary Taps on a Single Winding

The second method leaves the primary alone and takes intermediate connections out of the secondary winding, marked X1 to X5 or 1S1 to 1S4 depending on the manufacturer. A tap at a fraction of the full winding behaves as a shorter secondary: fewer turns, lower secondary voltage per ampere-turn, and therefore a higher secondary current for the same primary current.

Two consequences follow immediately, and both are routinely missed in offers:

  • Burden capacity scales with the tap. A full winding that holds 30 VA at 5 A develops 6 V across the burden. The half tap develops 3 V, which at 5 A is 15 VA. A relay or meter specified at 30 VA will not be driven by the half tap unless the tap is separately rated.
  • Accuracy is only promised for the full winding. IEC 61869-2 applies the declared class to the complete secondary winding unless the manufacturer states otherwise. A tap-specific class has to be asked for and written into the offer.

What the tap arrangement does protect is the short-time rating. There is still only one primary turn, or one bar through the window, and it carries the whole fault current in every connection. Thermal withstand therefore stays the same at every tap, which is exactly the opposite of the series/parallel compromise.

In practice the two methods are often combined. A typical cast resin CT of this kind carries a metering core with 0.2S class and taps at 200, 400 and 600 A, plus a protection core with no taps at 5P20 on the full 600 A winding. The metering core follows the load as it grows; the protection core keeps its maximum sensitivity. That is a rational division of labour and it is common in medium-voltage switchgear, where the panel has to accept a range of feeder duties before the load study is final.

Why the Accuracy Limit Factor Falls at a Lower Tap

For a protection core, the property that matters is not the class number alone but the secondary voltage the core can sustain before saturation. Manufacturers express this either as an accuracy limit factor at a stated burden or, for PX and TPS designs, as a knee-point voltage.

The required voltage at the accuracy limit is:

Vk required = ALF x Isn x (Rct + Zb)

where Isn is the rated secondary current, Rct the secondary winding resistance and Zb the rated burden impedance. The available knee-point voltage, for a given core, scales with the number of secondary turns in use. That is the whole mechanism: a shorter winding produces less volts per turn linked, so the core reaches saturation at a lower primary current.

Take a 600/5 A core, 5P20, 30 VA at 0.8 power factor, with a measured Rct of 1.0 ohm. The burden impedance is 30 / 25 = 1.2 ohm, so the required knee-point is 20 x 5 x (1.0 + 1.2) = 220 V. Now use the available taps, assuming the winding resistance and the knee-point voltage both follow the turns.

Connection Rct Knee-point at that tap ALF at 30 VA Primary current at the limit
Full winding, 600/5 A 1.00 ohm 220 V 20 12,000 A
Half tap, 300/5 A 0.50 ohm 110 V 12.9 3,870 A
Quarter tap, 150/5 A 0.25 ohm 55 V 7.6 1,140 A

Read the last column, not the fourth. At the quarter tap the unit is no longer a 20-times CT in any useful sense; it stops reproducing primary current faithfully at about 1,140 A. If the overcurrent setting was calculated on the assumption of 20 times 600 A, the protection is being asked to work at currents the core cannot transform.

The correction, in practice, is not to demand a higher ALF at every tap, because the low tap exists precisely to measure a low load. It is to make sure the protection core sits on the full winding, that the metering core is the one carrying the taps, and that any relay fed from a tapped winding has its settings reviewed against the tap-specific ALF rather than the nameplate ALF. The distinction between class accuracy and ALF is set out in this note on CT accuracy classes.

Bar chart showing how the primary current at the accuracy limit falls as a current transformer is connected to lower secondary taps

Thermal Withstand at Each Ratio

Short-time current is usually quoted as a current for a duration, most often 1 s or 3 s, with a separate peak value for the dynamic duty. The adiabatic check for the conductor is:

S = I x sqrt(t) / k

with S in square millimetres, I in amperes and k a material constant, about 143 for copper taken from 90 C to 250 C. Duration and current trade against each other by the square root, which is why 31.5 kA for 3 s and 54.6 kA for 1 s describe the same conductor, and why a unit rated 40 kA for 1 s really does need around 280 square millimetres of copper.

For a multi-ratio unit the check has to be run per connection, because the current path changes:

  • Series primary. Both sections carry the through current. Each section’s section-level limit stands, so the assembly’s through-current limit equals one section’s. This is the connection where a 25 kA nameplate can become a 12.5 kA reality.
  • Parallel primary. Each section carries half the through current, so the assembly’s limit is twice the section limit, at twice the ratio.
  • Secondary taps. The primary conductor is unchanged, so withstand is unchanged. The tap winding itself must carry Is x (tap inverse ratio) for the duration, which is why the tap conductor is sized for the secondary current and not for the burden.

The dynamic rating follows the thermal one. Peak withstand is normally 2.5 times the short-time current, and the mechanical force on the primary rises with the square of the current, so a unit that is acceptable thermally at the lower ratio may still be marginal mechanically if the peak figure is not stated.

Choosing the Ratios for a Real Feeder

Ratio selection starts from two currents: the highest sustained load and the lowest load that must still be metered accurately. The rated primary current is then set above the sustained load, typically 1.2 to 2.0 times it, so that the meter runs at a useful fraction of its range rather than in the bottom two percent where every CT is least accurate.

Worked example: a 2,000 kVA transformer on an 11 kV feeder. The full-load current is 2,000 / (1.732 x 11) = 105 A. A 150/5 A ratio gives 1.4 times the load, which is comfortable without pushing the meter into a low reading. If the feeder is expected to grow, a 2×300/5 A unit gives 150/5 A now and 300/5 A later without a crane, a shutdown or a new cable termination.

Item Value in this example Reason
Full-load current 105 A 2,000 kVA at 11 kV
Rated primary, first ratio 150 A 1.4 times the load
Rated primary, second ratio 300 A Headroom for a second transformer
Metering core 0.2S, 5 VA, tapped at 150/5 A S class keeps 1 to 120 percent in tolerance
Protection core 5P20, 15 VA, full winding No taps, so the ALF stays honest
Short-time current to specify Per connection, 1 s The board does not care which ratio you chose

Standard rated primary currents are 10, 12.5, 15, 20, 25, 30, 40, 50, 60 and 75 A, and their decimal multiples: 100, 125, 150, 200, 250, 300, 400, 500, 600, 750, 800, 1000, 1200, 1500, 2000, 2500, 3000, 4000 and 5000 A. Staying on the series matters more than it looks, because a non-standard ratio pushes the whole order into a special design and a longer lead time.

Where the load varies widely rather than growing, there is a third option: a single-ratio CT with an extended-range S class. A 0.2S or 0.5S core stays within its error limits from 1 percent to 120 percent of rated current, and some designs are offered with 200 or 300 percent extended range. For a feeder whose night load is 5 percent of its day load, an S class core on one ratio often beats a multi-ratio unit, because the accuracy band is guaranteed across the whole span rather than only at the tap you happen to be using. The trade-off is set out in this comparison of metering and protection CT cores.

Wiring Rules for Tapped Windings

Most of the damage done to multi-ratio CTs in service comes from the terminal box, not from the network. Four rules cover nearly all of it.

  • Burden or short the active pair. The two terminals in use must go to the meter, the relay or a shorting link. An open circuit on an energised CT lets the core drive the secondary voltage towards the knee point and beyond, which is dangerous to people and fatal to insulation.
  • Leave unused taps floating. They do not need shorting links. They are isolated turns on the same winding and carry no current of their own. Insulate them against accidental contact and leave them alone. The common instruction to short everything is wrong and creates the next problem.
  • Never parallel two taps of one winding. Two points on the same continuous coil joined together enclose a shorted section. Circulating current in that section heats the winding fast and can destroy the unit. Paralleling is only permissible between two separate, identical cores.
  • Earth the secondary at one point only. Bond the secondary circuit at the CT star point or at the panel, not at both, or a potential difference between the two earths will drive current through the measuring circuit.
Error in the terminal box What happens in service How it shows up
Unused taps shorted together Shorted turns, local overheating Thermal damage in one area, ratio drift, smell of hot resin
Active pair left open with primary energised High secondary voltage, insulation stress Flashover in the terminal box, meter or relay damage
Wrong tap connected to the meter Ratio error of exactly 2:1 or 4:1 Energy accounts that disagree with the sum of sub-meters
Secondary earthed at two points Circulating current in the measuring loop Small persistent error that changes with load elsewhere on the system

At commissioning, prove the ratio by primary injection rather than by reading the label. Apply a known current through the primary and read the secondary at the tap actually wired. A tap left on the wrong terminal shows up as a clean 2:1 error, which is easy to miss on a low load and expensive to find a year later in a billing dispute. The full set of ratios and burdens for a given design is listed in these CT ratio selection tables.

Ratio Matching Across Cores and Phases

A multi-ratio CT makes it possible to have different ratios in the same protection scheme without anyone noticing. Three cases are worth checking on every panel:

  • Differential and restricted earth fault zones. Every CT in the zone must sit on the same tap, and the relay’s ratio correction must be set against the ratio actually wired. One side on 300/5 A and the other on 600/5 A doubles the mismatch and produces spill current that looks like an internal fault at high load.
  • Residual or core-balance earth fault from three phase CTs. The three ratios must be identical, or the residual current at balanced load will not cancel. A 2:1 mismatch leaves a standing residual roughly equal to half the load current, which either desensitises the element or trips it.
  • Metering and protection sharing one core. Do not. A tap change made for a metering problem silently changes the protection characteristic. Separate cores, separate terminal blocks, separate records.

Record the taps in the protection settings file. Tap changes made years later during a load-growth project are one of the more common causes of a relay that mis-operates after an otherwise routine upgrade.

What the Enquiry Must State

Because the same model number can describe different performance depending on connection, the enquiry has to be written per ratio rather than per product. The list below is short enough to send as it stands.

Item What to write
Ratios required Every ratio, and which method produces it
Class per ratio 0.2S, 0.5, 5P20, 10P20, PX or TPS, stated for each tap
Burden per ratio VA at rated secondary current, at the stated power factor
ALF per ratio Or the knee-point voltage and excitation data for PX designs
Short-time current kA for 1 s or 3 s, per connection, plus the peak value
Core count How many cores, and which duty each one serves
Insulation Um, lightning impulse and power-frequency withstand
Installation Indoor or outdoor, mounting, terminal box orientation and cable entry
Environment Ambient range, altitude, pollution level at the site

Two of those lines do most of the work. The short-time current per connection prevents the series-connection surprise, and the class per tap prevents the burden surprise. Everything else the supplier can usually infer from the board and the single-line diagram. For high-current designs where the aperture replaces the primary winding entirely, the constraints shift again and are covered in this note on high current CT construction.

Frequently Asked Questions

Does a lower tap keep the same accuracy class?

Only if the manufacturer states a class for that tap. By default the class applies to the full secondary winding, and a tap below full winding carries less burden capacity and a lower accuracy limit factor. Ask for the tap-specific figures in writing.

Should the unused taps be shorted?

No. Unused taps are isolated points on the same winding and carry no current. Only the pair in use must be connected to a burden or shorted through a test link. Shorting unused taps together can create a closed loop inside the winding and is a recognised cause of overheating.

Can two taps be paralleled to increase the output?

Never on the same winding. Two taps on one continuous coil enclose a shorted section, and the circulating current in that section will damage the unit. Paralleling is only valid between separate, identical cores.

Why not simply buy a single-ratio CT?

If the load is stable and the fault level is known, a single ratio is cheaper, smaller and has one less thing to get wrong at commissioning. Multi-ratio units earn their price when the load is expected to grow, when the load study is not final at the time of ordering, or when a range of feeder duties has to be covered from one standard panel design.

Is the short-time rating lower at the low ratio?

It depends on the method. With primary series/parallel reconnection the series connection carries the full current in each half-winding, so the through-current capability in kiloamperes is about half that of the parallel connection. With secondary taps the primary conductor is unchanged and the short-time rating is the same at every ratio.

Can the tap be changed with the circuit energised?

No. The tap links are not designed as switching devices, and opening a live secondary circuit is precisely the condition that destroys insulation. Isolate the circuit, change the links, prove the new ratio by injection, and record the change.

Conclusion

A multi-ratio current transformer is a ratio device with a boundary, and the boundary is drawn by the connection method rather than by the model number. Primary reconnection keeps class, burden and accuracy limit factor identical at every ratio and gives up half the short-time withstand at the low ratio. Secondary taps keep short-time withstand identical at every ratio and give up burden, class and accuracy limit factor at each tap below full winding.

Write the enquiry per ratio, put the protection core on the full winding, keep the metering taps on their own core, and record the taps in the settings file. If you are specifying a unit for a board where the fault level, the load growth or the relay settings are still moving, send the single-line diagram and the expected load range, and the ratio, tap and core arrangement can be matched to it before the order is placed.