Instrument Transformer Standards: IEC 61869 vs IEEE C57.13

An instrument transformer nameplate is a compressed legal document. Two units can carry the same ratio, the same burden and the same accuracy figure, and still not be interchangeable, because one is described by IEC 61869 and the other by IEEE C57.13. The numbers are not the same kind of number. IEC states an accuracy class over a current range and a burden range; IEEE states an accuracy class at a defined burden, and for protection cores states a terminal voltage instead of an error at a multiple of rated current.

That difference causes more procurement argument than any genuine performance gap. A buyer comparing “0.2S 15 VA” against “0.3 B-0.5” is comparing a requirement that holds down to 1% of rated current with one that holds only from 10%, and a buyer comparing “5P20 30 VA” with “C200” is comparing an error limit at 5% with a terminal voltage at 10%. This article maps the two systems onto each other, part by part, so the comparison can be made on equal terms.

Side by side comparison matrix of IEC 61869 and IEEE C57.13 instrument transformer requirements

Two families, one physical device

IEC 61869 replaced the older IEC 60044 series and reorganised it around a two-stage structure. Part 1 holds the general requirements that apply to every instrument transformer: service conditions, insulation coordination, temperature rise, marking, and the general test framework. Each type-specific part then adds what is particular to that construction, including its own accuracy classes. A complete product specification is therefore always part 1 plus one other part, and quoting only one of them is incomplete.

IEEE takes a different route. C57.13 is a single standard that covers current and inductively coupled voltage transformers together, with accuracy classes, burdens, dielectric requirements and a test code inside it. The supporting documents around it are guides for field testing, grounding and high-voltage application rather than additional product requirements.

IEC 61869 part Title Edition
61869-1 General requirements Ed 2.0, 2023
61869-2 Additional requirements for current transformers Ed 1.0, 2012
61869-3 Additional requirements for inductive voltage transformers Ed 1.0, 2011
61869-4 Additional requirements for combined transformers Ed 1.0, 2013
61869-5 Additional requirements for capacitor voltage transformers Ed 1.0, 2011
61869-9 Digital interface for instrument transformers Ed 1.0, 2016
61869-10 Low-power passive current transformers Ed 1.0, 2017
61869-11 Low-power passive voltage transformers Ed 1.0, 2017
61869-13 Stand-alone merging unit Ed 1.0, 2021
61869-14 / -15 Current and voltage transformers for DC applications Ed 1.0, 2018
61869-20 Safety requirements for high-voltage applications Ed 1.0, 2025
61869-21 Uncertainty evaluation in the accuracy test Ed 1.0, 2025
61869-99 Glossary Ed 1.0, 2022

Two structural points are worth knowing before reading a certificate. The 2023 edition of part 1 absorbed the former part 6 on low-power instrument transformers, so a modern low-power specification cites part 1 rather than part 6. And the parts originally planned for electronic voltage and current transformers, 7 and 8, were not published as separate standards; their content is carried by the digital interface in part 9 and by the low-power parts 10 and 11. A supplier quoting “IEC 61869-8” is quoting something that does not exist.

The IEEE side of the shelf

IEEE document Scope Status
C57.13-2016 Requirements for instrument transformers: ratings, accuracy classes, burdens, dielectric, test code Active, revision in progress
C57.13.1-2017 Guide for field testing of relaying current transformers Active
C57.13.3-2014 Guide for grounding of instrument transformer secondary circuits and cases Active
C57.13.5-2019 Performance and test requirements above 115 kV Active
C57.13.7-2018 Current transformers with a maximum milliampere secondary current of 250 mA Active
C57.13.2-2005 Conformance test procedure Inactive, reserved
C57.13.6-2005 High-accuracy instrument transformers Inactive, reserved, content folded into C57.13

The inactive status of C57.13.2 is a practical detail rather than a legal one: a conformance test programme written around it may still be valid, but the document is no longer maintained, and the acceptance criteria it contains should be checked against the current C57.13 before it is written into a purchase order.

Reading an accuracy class in both systems

This is the part of the comparison that most often goes wrong, because the two systems describe accuracy at different points on the current axis. IEC 61869-2 states a ratio error and a phase displacement at 1%, 5%, 20%, 100% and 120% of rated current. IEEE C57.13 states a ratio error at 100% of rated current for metering classes, with a metering range that runs from about 10% to 100%, and states a terminal voltage for protection classes.

IEC class 1% In 5% In 20% In 100% In Phase at 100%
0.2 not specified ±0.75% ±0.35% ±0.2% ±10 minutes
0.2S ±0.75% ±0.35% ±0.2% ±0.2% ±10 minutes
0.5 not specified ±1.5% ±0.75% ±0.5% ±30 minutes
0.5S ±1.5% ±0.75% ±0.5% ±0.5% ±30 minutes
1.0 not specified ±3.0% ±1.5% ±1.0% ±60 minutes

Two consequences follow. First, IEEE class 0.3 is numerically tighter than IEC class 0.5 at rated current, but it carries no requirement at 5% or 1%, so the two cannot be ranked from their numbers. Second, the letter S in IEC is not “more accurate” but “accurate further down” — 0.2S holds 0.2% from 20% upward and adds limits at 1% and 5%, which is what a lightly loaded feeder needs and what IEEE handles through an extended-range option that has to be specified separately. The mechanics behind these numbers, at ordinary distribution ratios, are set out in this guide to CT accuracy class.

The class limits in both systems come with a range condition that is easy to miss. IEC 61869-2 applies the class only when the connected burden lies between 25% and 100% of the rated output; below 25% the unit is outside its tested range, and IEC provides a separate extended burden option that holds the class down to 1 VA for rated outputs of 15 VA or less. IEEE states the class at a standard burden, which is a single point rather than a band.

Burden: VA and ohms are the same quantity

The apparent incompatibility between “15 VA” and “B-0.5” disappears once the secondary current is known, because S = I²Z. IEEE standard burdens are ohmic values at the rated secondary current, so at 5 A every 0.1 ohm is 2.5 VA.

IEEE burden Impedance VA at 5 A VA at 1 A
B-0.1 0.1 Ω 2.5 VA 0.1 VA
B-0.2 0.2 Ω 5 VA 0.2 VA
B-0.5 0.5 Ω 12.5 VA 0.5 VA
B-0.9 0.9 Ω 22.5 VA 0.9 VA
B-1.8 1.8 Ω 45 VA 1.8 VA

The power factor attached to the burden also differs, and this is the part that is genuinely not interchangeable. IEEE metering burdens are stated at 0.9 power factor and relaying burdens at 0.5; IEC states the rated burden at 0.8 lagging. A burden that is within the VA limit but at a different power factor produces a different phase error, which is why a unit that passes on an IEC test bench can sit outside its class when connected to a burden specified the IEEE way.

Protection classes: 5P20 and C800 do not convert by table lookup

An IEC protection class states a composite error at a multiple of rated current with the rated burden connected. An IEEE relaying class states the secondary terminal voltage the unit will deliver at 20 times rated current without exceeding 10% ratio error, and the numerical suffix is that voltage in volts. The bridge between them is one equation:

Ut = n × Ins × (Rct + Zb), where n is 20, Ins is the rated secondary current, Rct is the secondary winding resistance and Zb is the connected burden in ohms.

Work the arithmetic for a 300/5 A unit marked 5P20, 15 VA, with a measured winding resistance of 0.4 Ω. The rated burden is 15/25 = 0.6 Ω, so Ut = 20 × 5 × (0.4 + 0.6) = 100 V, which lands on the C100 step. Change the burden to 30 VA with a winding resistance of 0.5 Ω and Ut = 100 × (0.5 + 1.2) = 170 V, which sits between C100 and C200. The class letter alone told you nothing; the burden and the winding resistance decided the answer.

IEC designation Rated burden Approximate IEEE equivalent
10P20, 25 VA 1.0 Ω at 5 A C100
10P20, 50 VA 2.0 Ω at 5 A C200
10P20, 100 VA 4.0 Ω at 5 A C400
10P20, 200 VA 8.0 Ω at 5 A C800

Those equivalences are widely used and are honest as far as they go, with two caveats. They compare against 10P20, because the C class is defined at 10% error; a 5P20 unit of the same burden must hold 5% where the C class allows 10%, so its true equivalent sits a step higher. And they assume a 5 A secondary. On a 1 A secondary the same C800 designation corresponds to 40 Ω but only 40 VA, which is one fifth of the VA available at 5 A — a difference that has caught out more than one retrofit.

Bar chart mapping IEC 5P20 and 10P20 burdens onto the IEEE C100 to C800 terminal voltage steps

Insulation: Um classes against voltage classes

IEC rates insulation by the highest voltage for equipment, Um, and then requires a lightning impulse and a power-frequency withstand that follow from it. IEEE rates by system voltage class and states a basic impulse level. The two describe the same dielectric duty with different bookkeeping.

IEC Um IEC lightning impulse IEC AC withstand ANSI voltage class ANSI BIL
7.2 kV 60 kV 20 kV 5 kV 60 kV
12 kV 75 kV 28 kV 15 kV 95 kV
24 kV 125 kV 50 kV 25 kV 125 kV
36 kV 170 kV 70 kV 34.5 kV 150 kV
40.5 kV 185 kV 85 kV 46 kV 200 kV

The practical trap is that “24 kV” in an IEC enquiry and “25 kV class” in an ANSI enquiry are not the same device. The BIL happens to coincide at 125 kV, but the current ratings, the creepage assumptions and the test voltages around them do not, and a unit built to one will rarely satisfy a witness test written to the other without a documented cross-check.

Test programmes: what is proved once, and what is proved on every unit

Test IEC 61869 IEEE C57.13
Lightning impulse Type test Design test
Power-frequency withstand Type test and routine test Design test and routine test
Partial discharge Routine measurement on medium-voltage units, limit in pC at a defined voltage Not a routine requirement in the base standard
Temperature rise Type test Design test
Short-time thermal and dynamic current Type test, Ith at 1 s and Idyn at 2.5 Ith Design test, mechanical rating
Accuracy Routine test on every unit, with type test evidence for the design Routine accuracy check, conformance programme per C57.13.2
Excitation and knee point Required data for PX and transient-performance classes Basis for calculating the C class; 45 degree tangent for non-gapped cores, 30 degree for gapped

The partial discharge row is the one that changes outcomes. A cast-resin unit built to IEC 61869-2 normally arrives with a measured PD value in picocoulombs at 1.2 Um/√3 for that serial number. The same unit offered to an IEEE specification may have no PD figure at all, because the standard does not require one routinely. If the project needs the number, it has to be asked for as a project requirement rather than assumed from the standard. What belongs in a type test, a routine test and a special test on a specific unit is covered in more detail in this instrument transformer testing guide.

Where GB/T 20840 fits

Chinese national standard GB/T 20840 is the adoption of IEC 61869 and is technically harmonised with it part by part, so a unit marked to GB/T 20840.2 is built to the same requirements as IEC 61869-2. What differs is the layer above: domestic utility specifications commonly add requirements the IEC text leaves open, including tighter partial discharge limits for some applications, extended creepage distances for polluted or coastal sites, and seismic qualification for regions with high design acceleration. A dual-marked unit is therefore not a compromise; it is an IEC unit plus evidence for the local additions.

For an export buyer the practical value is that a Chinese manufacturer can usually supply the IEC document set and the GB/T evidence together, and only the IEEE document set has to be produced separately — which is worth knowing when a project specifies both, as data-centre and utility projects increasingly do.

The same unit, described twice

Parameter IEC / GB description IEEE description of the same device
Ratio 300/5 A, 50 Hz 300:5, 60 Hz if built for it
Metering core 0.2S, 15 VA, FS 5 0.3 B-0.5
Protection core 5P20, 30 VA C200
Insulation Um 12 kV, LI 75 kV, AC 28 kV 15 kV class, 95 kV BIL
Short-time rating Ith 25 kA for 1 s, Idyn 62.5 kA Mechanical rating 62.5 kA peak
Frequency 50 Hz rated 60 Hz rated

Note what is missing from the right-hand column: there is no IEEE entry for the temperature rise limit in this comparison, because C57.13 references its own tables rather than IEC 61869-1, and the two do not produce identical limits for the same insulation class. A dual-marked unit must satisfy the stricter of the two, and the certificate should say which table was used.

Specifying across both systems

  • Name the standard, the part and the edition: “IEC 61869-2:2012 with IEC 61869-1:2023” is a specification; “IEC 61869” is not.
  • State the burden as VA at the rated secondary current and state the power factor, so the IEEE reader can convert it to ohms without guessing.
  • For protection cores, require the measured winding resistance and the excitation curve with the offer, because without them no C-class equivalence can be calculated.
  • For metering cores, state whether accuracy is needed at 1% or only from 5%, and whether the burden may fall below 25% of rated output.
  • State the frequency. A 50 Hz design run at 60 Hz has flux margin; a 60 Hz design run at 50 Hz does not, and this mistake survives every accuracy test at rated current.
  • Require partial discharge values per serial number at a stated test voltage, whichever standard is named.
  • Where both standards are named, require a cross-reference table in the offer that maps each IEC line to its IEEE equivalent, and reject any line that is left blank without an explanation.

Frequently asked questions

Is IEC 61869 stricter than IEEE C57.13?

Neither is stricter overall. IEC states accuracy over a range of currents and a band of burdens, which is a wider obligation; IEEE states a terminal voltage for protection cores, which is a more direct statement about behaviour during a fault. The honest comparison is per clause, not per standard.

Can a 5P20 CT be used where C400 is specified?

Only after the arithmetic. Calculate Ut = 20 × Ins × (Rct + Zb) with the actual burden and the measured winding resistance. If Ut reaches 400 V, the unit behaves as a C400 would at 10% error and will comfortably satisfy it at 5%. If Ut is 170 V, it will not.

Why does IEEE use 20 times rated current?

Because 20 times rated is the point at which the ratio error limit is defined for relaying classes, and it gives a single voltage number that a protection engineer can compare against the burden the relay and leads present. It is a convention that makes the calculation direct, not a statement about where saturation begins.

What does the S in 0.2S actually change?

The lower end of the specified range. Class 0.2 is specified from 5% of rated current; 0.2S is specified from 1%, with ±0.75% ratio error and 30 minutes of phase displacement at that point. The upper end is identical, so the S adds cost only when the load genuinely spends time near no load.

Does GB/T 20840 certification satisfy an IEC specification?

Technically the requirements are harmonised, so a GB/T 20840.2 unit is built to the same clauses as IEC 61869-2. Whether it satisfies a particular contract depends on the contract’s wording and on any additional local requirements layered above the standard, so the certificate and the type test reports should be checked line by line rather than assumed equivalent.

Which standard applies to a unit with a digital output?

IEC 61869-9 governs the digital interface, used together with part 1 and the relevant low-power parts, 10 and 11, or with part 2 and part 3 for units with an analogue secondary plus a merging unit under part 13. IEEE C57.13 has no equivalent digital-interface clause; C57.13.7 covers milliampere-level analogue outputs instead.

The standards question is really a documentation question. A supplier who can produce the part numbers, the editions, the measured PD values and the excitation curves has already done the hard part; the buyer’s job is to ask for them in the enquiry rather than after the witness test. For the product side, the instrument transformer range is documented to IEC 61869 and GB/T 20840, and the comparison of transformer standards covers the power transformer equivalents of the same three families.