Above roughly 1,000 A, the ratio on a current transformer stops being a design decision. Whatever the busbar carries is the ratio: one turn through the window, several hundred turns on the core, and the “3,000/5 A” on the nameplate is a consequence of the switchgear rather than a choice. What is left to design is everything the ratio does not describe — the window that has to swallow the conductor, the thermal rating that has to survive the board’s fault level, the core that has to stay within class at 1% of a very large rated current, and the secondary circuit that has to carry the signal down a long cable.
That is why a 3,000 A unit is not a scaled-up 300 A unit. At low ratios the primary winding is the dominant piece of engineering; at high ratios it disappears entirely and the mechanical and thermal design of the aperture takes over. Enquiries that go wrong are almost always ones where a 300 A data sheet was copied and the ratio edited, leaving a window that will not accept the busbar and a thermal rating that is a fraction of the board’s fault level.

Why the ratio stops being the variable
IEC 61869-2 fixes the standard rated primary currents at 10, 12.5, 15, 20, 25, 30, 40, 50, 60 and 75 A and their decimal multiples, with 1 A or 5 A on the secondary. A 3,000 A ratio is simply 40 times the 75 A series. The standard also fixes the relationship the designer cannot escape: rated continuous thermal current defaults to the rated primary current, and a higher continuous rating must be one of the preferred values of 120%, 150% or 200% of it.
So for a high-current unit, three quantities are already given by the installation before the CT is chosen:
- Rated primary current — the busbar’s design current, or the next standard value above it.
- Rated short-time thermal current — the switchgear fault level at the same duration, standardised at 1 s.
- Rated dynamic current — 2.5 times the short-time thermal current, unless the purchaser specifies otherwise.
What the manufacturer still controls, and what the buyer must therefore state or accept as a default, is the aperture, the core, the secondary winding and the insulation. Those four decide whether the unit fits, whether it survives, and whether it stays inside its accuracy class.
Three constructions, and which one you get at 3,000 A
IEC 61869-2 separates current transformers by construction because the construction determines how the ratio is produced. The distinction matters most at high current, where two of the four categories are effectively unavailable.
| Construction | How the ratio is made | Practical current range | What drives the design |
|---|---|---|---|
| Wound primary | Multiple primary turns through the core | Up to a few hundred amps | Turns balance, winding space |
| Bar primary | A single factory-fitted bar, one turn | Roughly 400 A to 2,500 A | Bar section for Ith, window clearance |
| Window or through type | No primary at all; the installation’s conductor passes through | 1,000 A upward, no upper limit in principle | Aperture size, conductor centring, core size |
| Bushing type | The primary is the bushing conductor of the equipment | Any, where a bushing already exists | Bushing geometry, mounting interface |
At 3,000 A a factory bar becomes a liability. The bar alone would have to be around 1,500 mm² of copper to carry the continuous current at ordinary air-cooled density, and a manufacturer would be shipping a busbar inside a moulding rather than a transformer. The installation already has a busbar of that size, so the sensible product is an aperture the busbar passes through, with the CT’s job reduced to the core, the secondary and the insulation around the hole.
A bushing-type current transformer deserves a note of its own: IEC 61869-1 explicitly brings it into scope even though it has no primary insulation level of its own, because it is installed in a system rated at 1 kV or above. In a metal-clad switchgear panel the bushing CT is usually the cheapest way to instrument a high-current circuit, provided the bushing dimensions are known before the panel is ordered.
The window drawing decides the order
For a through-type unit the aperture is the first drawing to settle, and it is settled by the busbar arrangement rather than by electrical calculation. Four things have to fit inside or around the hole:
- The conductor bundle for one phase — for example three 100 × 10 mm bars on edge, a 300 mm wide by 10 mm thick stack.
- Clearance between the bundle and the core, so that the primary does not touch the moulding and so that insulation can be applied.
- The phase-to-phase spacing the switchgear imposes, which limits how much moulding can surround the core.
- The secondary terminal box and its cable entry, which must not end up inside the busbar’s field or block a fixing.
A rectangular window is almost always the right shape for busbar work, because busbar is rectangular and a round window large enough to take a 300 mm stack becomes unnecessarily tall. The round window that suits a cable-fed unit at 630 A wastes vertical space at 3,000 A and pushes the core further from the conductor, which costs accuracy.
Centring matters more than most specifications admit. The core sees the flux produced by the primary conductor, and a conductor hugging one side of the window produces a less uniform field than one in the middle. On a measuring core the effect appears directly as ratio error, and on a large window the difference between a centred and an off-centre bar is measurable. IEC 61869-2 requires the manufacturer to state the position assumed, which is why the busbar drawing belongs in the enquiry and not in a later email.

Turns, and what the secondary winding costs you
The secondary turns count is fixed by the ratio: 3,000/5 A needs 600 turns, 3,000/1 A needs 3,000. At high ratios the 1 A secondary becomes a winding-space problem rather than an electrical one, because five times the turns must fit around the same core window, or the core must grow to make room. That is why high-ratio 1 A units are physically larger than their 5 A equivalents, and why a buyer who specifies 1 A for a 5,000 A circuit should expect a bigger, heavier and more expensive device.
In return, the 1 A secondary removes most of the lead burden. IEC 61869-2 goes further and makes 1 A the standard secondary current for protective current transformers with transient performance, because the lower current is what makes a long secondary run feasible without an oversized core.
| Typical rated primary | Secondary turns at 5 A | Typical construction | Typical window |
|---|---|---|---|
| 630 A | 126 | Bar primary, 40 × 10 mm bar | 60 × 60 mm round |
| 1,250 A | 250 | Bar primary or through type | 80 × 80 mm round, or 120 × 60 mm |
| 2,000 A | 400 | Through type, one busbar per phase | 160 × 80 mm |
| 3,150 A | 630 | Through type, two bars per phase | 200 × 120 mm |
| 5,000 A | 1,000 | Through type, three or four bars, or a tube | 300 × 150 mm |
Thermal duty: Ith, Idyn and the bar that carries them
The rated short-time thermal current is the number that most often disqualifies a cheap offer. The standard duration is 1 s, and the rating must cover the switchgear’s fault level at the same duration. Converting between durations is arithmetic rather than judgement, because the admissible quantity is I²t: a board rated 31.5 kA for 3 s demands 31.5 × √3 = 54.6 kA for 1 s, and a CT rated 40 kA for 1 s is not adequate for it.
For a bar-primary or through-type unit the heat is generated in the primary conductor, so the thermal rating is really a statement about conductor section. The adiabatic check from IEC 60364-5-54 applies directly: S = I√t / k, with k = 143 A·s1/2/mm² for copper taken from 90 °C to 250 °C, valid for durations up to about 5 s.
| Ith at 1 s | Minimum copper section | Equivalent at 3 s |
|---|---|---|
| 20 kA | 140 mm² | 11.5 kA |
| 25 kA | 175 mm² | 14.4 kA |
| 31.5 kA | 220 mm² | 18.2 kA |
| 40 kA | 280 mm² | 23.1 kA |
| 50 kA | 350 mm² | 28.9 kA |
Read the table both ways. A 40 kA/1 s rating and a 23.1 kA/3 s rating require the same 280 mm² of copper, so a specifier who converts the board’s 3 s duty into 1 s gets an honest comparison between two offers. A unit quoting 40 kA for 1 s against a board needing 54.6 kA for 1 s is undersized by 27%, and no amount of core quality compensates for a bar that will reach its temperature limit.
There is a subtlety specific to through-type units: the CT has no primary of its own, so the manufacturer must state which primary conductor the Ith applies to. A rating quoted for a single 100 × 10 mm bar is not a rating for a three-bar bundle, and the enquiry should either name the conductor or require the manufacturer to confirm the rating against the actual arrangement.
Continuous duty is the other half. Air-cooled copper busbar in still air is normally run at roughly 1.5 to 2.5 A/mm², so a 4,000 A circuit needs in the order of 1,600 to 2,600 mm² of copper — two 100 × 10 mm bars per phase at the upper density. That is the conductor the window has to accept, and it is why the window drawing and the thermal rating cannot be specified independently.
Mechanical force, and why the core is clamped rather than cantilevered
The rated dynamic current is a mechanical statement. At 2.5 times a 40 kA thermal rating the peak is 100 kA, and two parallel bars carrying that peak in the same direction repel each other with a force of 2 × 10-7 × ip² / d newtons per metre, where d is the spacing. At 100 mm spacing and 100 kA peak, that is about 20 kN per metre of busbar — two tonnes of force on every metre, reversing twice per cycle.
The CT survives that only if the core and the moulding are treated as a rigid body. Cast resin helps, because the core, the windings and the insert are encapsulated into one block, but the block still has to be bolted to a support that does not flex. Three practical consequences follow. Mounting bolts must be sized for the short-circuit torque, not the static weight. The secondary terminal box must not be the only thing holding the winding in place. And on a through-type unit the CT must not be used as a busbar support, because the busbar’s own deflection under fault will then load the moulding directly.
Holding 0.2S accuracy at 1% of 3,000 A
This is where high-ratio metering cores become expensive, and where the class designation stops being a label and becomes a core specification. A 0.2S core must hold ±0.75% at 1% of rated current with 30 minutes of phase displacement. On a 3,000/5 A unit, 1% is 30 A primary and 50 mA secondary. A 0.2% error at that point leaves roughly 0.1 mA for the excitation current — a tenth of a milliamp, in a core that must not saturate at 20 times rated current with the connected burden.
Nothing about that is achievable by choosing a better label. It is achieved by core section, core material and a winding that fits — the same mechanics that CT accuracy class describes at ordinary ratios. It is also why a 0.2S high-ratio unit can be two or three times the mass of a 0.5 class unit of the same ratio. Two further rules apply to measuring cores at this size:
- The class limits hold between 25% and 100% of the rated burden. Below 25% the unit is outside its tested range, so a 30 VA core feeding a 0.5 VA electronic meter is as much a mismatch as an overloaded one. IEC 61869-2 provides an extended burden range down to 1 VA for rated outputs of 15 VA or less, and that option has to be asked for.
- A metering core carries an instrument security factor. At FS times rated current the composite error is at least 10%, so FS 5 on a 3,000 A unit means the secondary stops tracking above 15 kA and the meter is protected. Specifying FS 10 instead of FS 5 triples the fault current the meter sees.
Protection cores follow different arithmetic, which is the dividing line between metering and protection CTs. A 5P20 core on a 3,000 A unit guarantees 5% composite error up to 60 kA, which is a statement about the core’s capability at 20 times rated current with the rated burden connected — not a promise about any other burden. If the actual through-fault current is 70 kA, the core saturates before the guarantee ends and the relay may under-reach. For differential protection on a high-current circuit, a PX or TPS core with a specified knee point and winding resistance is usually the correct answer rather than any P class.
Burden and lead length: 5 A against 1 A
Secondary burden is the sum of the relay or meter impedance, the terminal and test-block resistance, and the lead loop. Only the lead term scales with distance, and it scales with the square of the secondary current, which is what makes the 1 A secondary worth its extra turns on a long run.
| Copper conductor | Loop resistance, 100 m of conductor | Burden at 5 A | Burden at 1 A |
|---|---|---|---|
| 2.5 mm² | 0.70 Ω | 17.5 VA | 0.7 VA |
| 4 mm² | 0.44 Ω | 11.0 VA | 0.44 VA |
| 6 mm² | 0.29 Ω | 7.3 VA | 0.29 VA |
| 10 mm² | 0.18 Ω | 4.4 VA | 0.18 VA |
The table also explains a common specification error: a 3,000/5 A CT ordered with a 15 VA measuring core, installed 50 m from the panel with 2.5 mm² cable, arrives at the meter with 17.5 VA of lead burden before the meter itself is counted. The core is overloaded, the ratio error grows, and the installation is out of class before it is commissioned.
Proving it without 3,000 A of test current
Primary injection at 3,000 A is a laboratory exercise, so a high-current CT is normally verified by equivalent methods. The routine programme is a power-frequency withstand on the primary, a partial discharge measurement, a polarity check, a secondary winding resistance measurement, and a ratio and phase-displacement check by the voltage method or by comparison against a reference unit. IEC 61869-2 permits these equivalent methods, and the test report should name the method used. The wider programme, including what belongs in a type test as opposed to a routine test, is set out in this instrument transformer testing guide.
For protection cores, the excitation curve is the evidence that matters. The knee point is defined as the point where a tangent to the excitation curve makes 45 degrees with the horizontal for a non-gapped core, and 30 degrees for a gapped core. Two units of the same class and ratio can have very different knee points, and the one with the lower knee point is the one that will saturate first during a fault with DC offset.
Partial discharge on a cast-resin high-current unit is measured at 1.2 Um/√3, and on a large aperture the measurement is worth reading rather than filing: voids in a thick casting around a big window are the classic mechanism by which a unit passes routine tests and fails in service.
Specification lines for the enquiry
| Line | What to state | Default if left open |
|---|---|---|
| Ratio and secondary | 3,000/5 A, or 3,000/1 A where the run exceeds 50 m | 5 A, with the lead burden unaccounted for |
| Construction | Through type, window 200 × 120 mm, busbar drawing attached | Bar primary that will not accept the bundle |
| Thermal rating | Ith 54.6 kA for 1 s, Idyn 137 kA peak | Quoted at 1 s without conversion from the board’s 3 s duty |
| Continuous rating | 120% of rated primary, stated explicitly | Rated primary only, unsuitable for cyclic overload |
| Measuring core | 0.2S, 15 VA, FS 5, extended burden range down to 1 VA | 0.5 class with a narrow burden band |
| Protection core | 5P20 30 VA, or PX with Vk and Rct stated | An ALF that does not cover the fault level |
| Insulation | Um 12 kV, LI 75 kV, AC 28 kV, creepage for the site’s pollution level | Indoor creepage on an outdoor installation |
| Tests | Routine report per serial number, PD value in pC, excitation curve for each protection core | Certificate of conformity without measured values |
Frequently asked questions
At what current does a window-type CT replace a bar-primary CT?
There is no standard threshold, but the economics turn at roughly 1,000 to 1,250 A. Below that a factory-fitted bar is compact, cheap and gives a defined primary conductor for the thermal rating. Above it the bar becomes heavy, the window becomes the dominant dimension and the installation already owns a conductor that can pass through the aperture.
Can a 5 A secondary be used on a long run?
It can, but the lead burden grows with the square of the current, so 100 m of 2.5 mm² conductor costs 17.5 VA at 5 A and 0.7 VA at 1 A. Where the panel is far from the CT, specify 1 A and accept the larger core, or move the measuring point closer and use a transducer.
Why is the rated dynamic current 2.5 times the thermal current?
Because the peak of a fully offset fault current is roughly 2.5 times its rms value, and it is the peak that produces the mechanical force between conductors. IEC 61869-2 sets 2.5 as the standard ratio and allows a different value to be marked where the purchaser requires it.
Does the position of the busbar inside the window change the accuracy?
Yes. A conductor in the centre of the aperture produces a more uniform field in the core than one pressed against the side, and the difference appears as ratio error on a measuring core. Quote the busbar arrangement with the enquiry so the manufacturer states the position assumed.
What accuracy class is realistic on a 3,000 A metering core?
0.2 or 0.2S is routine at high ratios, but it is bought with core mass. If the load never falls below 10% of rated current, class 0.5 is a smaller and cheaper core for the same duty, and the saving is real rather than marginal.
How is a high-current CT tested before dispatch?
By power-frequency withstand, partial discharge measurement, polarity, winding resistance, and ratio and phase displacement by an equivalent method such as the voltage method or comparison against a reference transformer. The report should state the method, because primary injection at rated current is not practical above a few hundred amps.
High-current instrument transformers sit between two worlds: they are electrical devices whose accuracy is decided by the core, and mechanical devices whose survival is decided by the aperture and the mounting. Getting the enquiry right means stating both. The current transformer range covers indoor and outdoor cast-resin units across these constructions, and the article on CT construction details explains how the core and insulation are built for each one.