A current transformer with an open secondary is not idle equipment. With the primary energised and the secondary open, the whole primary current becomes excitation current: the core saturates hard, the flux collapses twice per cycle, and the terminals develop voltage spikes in the kilovolt range. The same circuit, shorted and earthed at one point, carries a couple of amperes at a few volts and is safe to work on.
That contrast is most of secondary-circuit design. This guide covers the earthing rule for current transformers and voltage transformers, why the rule is one earth point rather than two, what an open CT circuit actually does, how PT fusing differs in direction, and how conductor size, burden and polarity decide whether a relay sees what the primary is doing.
The Single Earth Point Rule, and Why Not Two
IEC 61869-2 for current transformers and IEC 61869-3 for voltage transformers both require the secondary circuit to be earthed, and both leave the location to the installation. The reason is not measurement. Capacitive coupling between the primary and secondary windings can float the entire secondary circuit — terminal block, relay coils, meter movements, the lot — at close to primary potential. A CT on a 10 kV feeder can therefore put kilovolts on a circuit that everyone treats as safe to touch.
One earth connection removes that exposure by holding the secondary at earth potential. It also gives the insulation of the secondary wiring a defined working voltage instead of an undefined one. The exception is a CT with an earthed electrostatic shield between primary and secondary: the shield already intercepts the coupling, and the secondary may then be left unearthed, which is the arrangement used for some low-level and laboratory transformers.
What an Unearthed Secondary Floats At
Nothing visible happens. The secondary sits at whatever potential the coupling and the connected burden allow, and the first indication of a problem is usually a shock from a terminal that should have been dead, or a relay input card failing after a primary insulation fault. Insulation co-ordination in the panel assumes the secondary is at earth potential, so an unearthed secondary quietly invalidates the assumption rather than announcing it.
What a Second Earth Actually Does
A second earth turns the neutral conductor into one leg of a loop that closes through the station earth grid. The driving voltage is the potential difference between the two earth points during a fault — a few volts is enough, because the loop impedance is also only a few tenths of an ohm. Three effects follow:
- The secondary current divides between the measuring circuit and the earth path, so every reading is low by an amount nobody can calculate from the drawing.
- Zero-sequence current from an earth fault elsewhere in the station circulates through the neutral and appears as residual current in a healthy feeder.
- Directional and differential elements see a phase shift that depends on the grid, not on the primary circuit, which is exactly the sort of error that produces a trip during a through-fault and no trip during an internal one.
The practical consequence for a differential scheme is that both sets of CTs are bonded at one common point only, usually at the relay panel, and that this single bond is the one earth for the whole comparison circuit. Separate earths at each CT terminal box defeat the scheme even though each earth looks correct on its own.

What an Open CT Secondary Does
A CT is a current source. Its secondary current is fixed by the primary current and the ratio, and the secondary voltage is whatever is needed to push that current through the burden. Open the circuit and the current has nowhere to go, so the core is driven far into saturation by a primary ampere-turn product that was designed to be balanced by the secondary. Twice per cycle the core comes out of saturation, the flux changes almost instantaneously, and the winding turns generate a voltage spike limited only by stray capacitance and the insulation that is about to fail.
The voltage is not a smooth few hundred volts. It is a train of steep spikes with peak values in the kilovolts, which is enough to break down control cable insulation, flash across a terminal block and injure anyone in contact with the panel. Core loss and winding loss rise at the same time, so the transformer also heats.
| Condition | What the secondary sees | Consequence |
|---|---|---|
| Secondary open, primary at rated current | Full primary current becomes excitation current, core deeply saturated | Kilovolt spikes at the terminals, insulation stress in the whole secondary circuit |
| Open circuit held for minutes | Iron and copper loss concentrated in a small core | Overheating, winding insulation degradation, possible winding failure |
| Burden unplugged with primary live | Same as an open circuit, without warning | Arc at the plug, hazard to the person removing it |
| Unused core left open | Same failure mode on a core nobody is watching | Terminal block damage that is found only at the next test |
| Secondary shorted, primary live | Normal operating condition | None; this is the safe state for maintenance |
Isolating a CT Secondary Safely
The order of operations matters more than the tools. Short the secondary first, at the test terminal block, using the shorting screw or a purpose-made shorting link; then open the circuit to remove the burden. Restore in the opposite order. Removing a burden first, even briefly, is the same electrical event as an open circuit and produces the same spikes.
- Short each phase to the star point for a star-connected set, and do not rely on disconnecting the neutral as a substitute for shorting.
- Short unused cores at the terminal box and earth them at that same point; an unused core is still a live current source.
- On a multi-tap CT, short the tap pair in use. Leave the unused taps open: shorting across taps changes the effective ratio and the accuracy.
- Treat the secondary terminal cover as a safety device. It exists to stop a tool bridging the terminals while the primary is live.
- Low-voltage CTs below 1 kV are normally left unearthed, because the insulation between primary and secondary is generous and earthing invites noise. The no-open-circuit rule still applies without exception.
PT Secondary Circuits: Fuse, Do Not Short
A voltage transformer is the opposite device. Its secondary behaves as a voltage source with low internal impedance, so a short circuit draws a large current and destroys the winding within seconds. That is why the PT secondary is protected by fuses or miniature circuit breakers and why the CT secondary never is: a fuse in a CT circuit would open at exactly the moment the CT needs a closed path.
Two practical points follow. First, the earthing point: the secondary star point of a PT is earthed at one point, normally in the transformer terminal box, for the same reason as a CT. Second, the fusing arrangement depends on the system earthing. In an isolated or resonant-earthed system a phase-to-earth fault elsewhere can put close to full phase-to-phase voltage across a single fuse, so both poles are fused. In an effectively earthed system single-pole fusing with the earthed pole solid is common practice.
Where Ferroresonance Enters
Fusing a PT does not make it immune to overvoltage. An electromagnetic PT saturating against the grading capacitance of the system can sustain a ferroresonant oscillation, and the current that flows is limited by the capacitance rather than by the fault, so no fuse operates. The countermeasures — damping resistors, a properly rated voltage factor, avoiding a single-phase PT on an isolated system where a three-phase unit is needed — belong to the fuse selection exercise, not to the earthing rule. The two are usually considered together because both show up as a PT that runs hot or a fuse that fails for no obvious reason.
Star, Open-Delta and Broken-Delta PT Connections
The connection decides which voltages exist at the secondary terminals, and the choice is driven by whether the protection needs residual voltage.
| Connection | Phase-to-earth | Phase-to-phase | Residual 3U0 | Units | Typical duty |
|---|---|---|---|---|---|
| Three single-phase PTs, star primary, star secondary plus broken delta | Yes | Yes | Yes, from the auxiliary winding | 3 | Unearthed systems, earth-fault detection, metering and protection |
| Three-phase five-limb unit | Yes | Yes | Yes, internally | 1 | Metal-enclosed panels where space is limited |
| Two single-phase PTs in open delta (V connection) | No | Yes | No | 2 | Metering on a system where earth-fault detection is done elsewhere |
| Three-phase three-limb unit | Yes | Yes | Not reliably | 1 | Balanced loads; zero-sequence flux has no return path in the core |
The broken-delta winding is the reason the panel can detect an earth fault at all. Three auxiliary windings rated 100/3 V are connected in series and the two ends brought out; in a healthy system the three phasors cancel and the terminals read close to zero. During a solid single-phase earth fault the two healthy phase-to-earth voltages rise by the square root of three, the cancellation fails, and the terminals deliver about 100 V of residual voltage to the relay.

That same fault is why the voltage factor matters. A PT winding connected phase-to-earth in an isolated or resonant-earthed system has to carry 1.9 times its rated voltage for up to 8 hours without losing accuracy or overheating, because the fault may persist until a crew finds it. A winding bought at 1.2 times rated — the default when nothing is specified — is over its thermal rating long before then. Where earth faults trip automatically, the same 1.9 factor applies for 30 seconds instead of 8 hours, which is a much cheaper winding to build.
CT Secondary Wiring: Conductor Size, Burden and 1 A versus 5 A
Burden is the sum of everything the secondary has to drive: relay current inputs, meters, transducers, terminals and, often the largest term, the cable. Lead resistance is easy to underestimate because it is quoted in ohms per kilometre and the run is quoted in metres.
| Conductor, copper | Resistance at 20 °C | VA in a 100 m loop at 5 A | VA in the same loop at 1 A |
|---|---|---|---|
| 2.5 mm² | 7.0 Ω/km | 17.5 VA | 0.7 VA |
| 4 mm² | 4.4 Ω/km | 11.0 VA | 0.44 VA |
| 6 mm² | 2.9 Ω/km | 7.3 VA | 0.29 VA |
Two conclusions follow. A 2.5 mm² run of 100 metres consumes more burden than most static relays, so a CT rated 15 VA may already be fully used before the relay is counted. And because loss rises with the square of current, a 1 A secondary cuts the lead loss by a factor of 25 for the same conductor — the reason long runs to a remote control building use 1 A CTs and short runs inside a switchgear line-up use 5 A.
Size the CT rated burden at least 25 percent above the calculated total, keep the cable twisted or shielded, and earth the shield at the panel end only. Route the secondary cable away from the LV power and variable-speed drive cables it will otherwise pick up noise from; a few millivolts of induced noise is a real error on a 1 A circuit.
Polarity, S1/S2 and Star-Point Location
Polarity markings are not decorative. P1 and S1 are the same end of the transformer, so current entering P1 leaves from S1 in phase. Reverse the secondary connection and every directional or differential element sees a 180-degree shift, which reads as a fault in the reverse direction or as a differential current that does not exist. Check polarity with a DC kick test or a primary injection set before the panel is energised, not after the first trip.
Where the star point is bonded depends on the scheme. A single set of CTs feeding protection and metering is bonded at the CT terminal box. A differential scheme bonds both sets at one common point, usually the relay panel, so that the comparison circuit has one earth reference. Metering cores and protection cores are separate windings with different saturation behaviour and are never paralleled; the accuracy class of a metering core and the accuracy limit factor of a protection core are different specifications, and swapping the two produces a meter that reads low at normal load or a relay that under-reaches on a close-in fault.
Commissioning Checks for Secondary Circuits
- Continuity end to end on every core, with the far end disconnected from the relay.
- Insulation resistance of the secondary wiring to earth, typically at least 1 MΩ at 500 V DC with the relay disconnected — a low reading usually means a wet terminal box rather than a bad cable.
- One earth point confirmed by lifting the bond and measuring, not by reading the drawing.
- Polarity check on each core against the primary marking.
- Ratio check by primary injection at a current high enough to be read accurately, or by secondary injection with the CT ratio taken from the nameplate.
- Burden measurement with the actual connected devices in circuit, compared against the rating the accuracy class was guaranteed at — the class only holds between 25 and 100 percent of rated burden.
- Phase identification at the relay terminals, matched against the primary phases.
- As-built record of the earth point location, since the next crew will not find it by inspection.
The same checks apply to the CT/PT set in a KYN28 panel, where the secondary wiring also has to survive the movement of a withdrawable truck. Strain relief at the connector and a shorting arrangement that operates before the connector separates are part of the design, not an accessory.
Field Faults and Their Symptoms
| Symptom | Likely cause | Where to look first |
|---|---|---|
| One phase reads low, the other two normal | Secondary terminal not tightened, or a shorting link left in place | Terminal block, test links |
| Residual current in a healthy feeder | Second earth point, or a core shorted to the star point | Earth bonds in the terminal box and at the panel |
| Differential relay trips on through-fault | Star points earthed at each CT instead of one common point | Bonding arrangement at both ends |
| PT fuse fails repeatedly | Ferroresonance, undersized fuse, or a shorted secondary circuit | Fuse rating against the PT rating, damping |
| Residual voltage present with no fault | Broken-delta winding loaded by a relay with too low an impedance, or a reversed unit in the set | Polarity of each unit, relay burden |
| Relay reads correct current but wrong phase angle | Reversed polarity on one core | S1/S2 at the CT, P1/P2 orientation |
A secondary circuit is cheap to get right at the factory and expensive to diagnose in service, because every fault looks like a protection fault until the wiring is proved. Earthing at one point, shorting before opening, fusing the PT and never the CT, and keeping the burden calculation honest cover nearly all of it.
FAQ
Why must a CT secondary never be open-circuited?
Because the CT is a current source. With the secondary open, the full primary current becomes excitation current, the core saturates and the flux collapses twice per cycle, generating kilovolt spikes that can break down insulation and injure people. Short the secondary before working on it.
Should the CT secondary be earthed at the switchgear or at the relay panel?
Either, as long as it is earthed once. Practice favours the switchgear end for a single set of CTs, because it keeps the station earth grid out of the measuring circuit. For differential protection the two sets are bonded at one common point, usually the relay panel.
Can a CT secondary be fused?
No. A fuse in a CT secondary is a future open circuit, and it will open when the CT most needs a closed path. Fuses belong on the PT secondary, where a short circuit is the hazard and an open circuit is harmless.
Why is the PT voltage factor sometimes 1.9 and sometimes 1.2?
The factor describes the overvoltage a phase-to-earth winding must survive. In an isolated or resonant-earthed system with no earth-fault tripping, a single earth fault holds the healthy phases at 1.9 times rated voltage for up to 8 hours, so the winding must be built for it. Where faults are tripped automatically, the same factor applies for 30 seconds.
What causes residual voltage in a healthy system?
Unbalance in the three phase-to-earth capacitances, third-harmonic content, a reversed unit in the PT set, or a broken-delta winding loaded below its rated burden. Measure the residual with the relay disconnected before condemning the PTs.
Is 5 A or 1 A better for a CT secondary?
1 A for long cable runs, because the lead loss falls by a factor of 25 for the same conductor. 5 A for short runs inside a switchgear line-up, where the higher current gives better immunity to noise and the burdens are small.
If you are specifying instrument transformers for a new panel, matching the CT and PT set to the relay scheme at the drawing stage avoids most of the field faults in the table above. The CT and PT selection for KYN28 and RMU panels walkthrough covers the ratio, class and burden side of the same design, and the instrument transformer test sequence covers what to expect at FAT.